1-528 XPM card replacement procedures
NT2X70
in an SMU
(continued)
Replacing an NT2X70 card in an SMU
At your current location:
1
2
At the MAP terminal:
3
4
297-8021-547 Standard 14.02 May 2001
Proceed only if you have been directed to this card replacement procedure
from a step in a maintenance procedure.
CAUTION
Loss of service
When replacing a card in the SMU, ensure that the unit
where you are replacing the card is inactive and that the mate
unit is active.
Get a replacement card. Verify that the replacement card has the same
product engineering code (PEC), including suffix, as the card to be removed.
Ensure the PM level of the MAP terminal is currently displayed and post the
SMU by typing
>MAPCI;MTC;PM;POST SMU smu_no
and pressing the Enter key.
where
smu_no
is the number of the SMU to be posted
Example of a MAP response:
SMU
SysB
ManB
PM
3
SMU
0
SMU 0 ISTb
Links_OOS:
Unit0:
Inact SysB
Unit1:
Act
InSv
By observing the MAP display, ensure the card to be removed is on the
inactive unit.
If faulty card is on
active unit
inactive unit
Offl
CBsy
ISTb
0
1
0
0
0
0
CSide 0, PSide 0
Do
step 5
step 8
InSv
2
13
1
7