Nortel DMS-100 Series Replacement Procedures page 954

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-922 XPM card replacement procedures
NT6X21
in a STAR or RLD
Replacing an NT6X21 card in a STAR or RLD
At your current location
1
2
3
At the MAP terminal
4
5
297-8021-547 Standard 14.02 May 2001
(continued)
Get a replacement card. Make sure the replacement card has the same
product equipment code (PEC), including suffix, as the card that is to be
removed.
Make DIP switch changes for the line card.
If the line card code is
AA, AB, AC
AD
Make DIP switch settings as described in the "Recommended NT6X21AD
DIP switch settings" table located in the "Star Remote System hardware"
chapter in this manual.
To access the LTP level of the MAP terminal and post the line associated with
the card to be replaced, type
>MAPCI;MTC;LNS;LTP;POST L site frame unit lsg ckt
and press the Enter key.
where
site
is the name of the site where the STAR is located
frame
is the frame number of the STAR with the faulty card
unit
is 0 for the STAR
lsg
is the number of the line subgroup with the faulty card (0-35)
ckt
is the number of the circuit associated with the faulty card (0-31)
Example of a MAP response:
LCC PTY RNG .....LEN.......... DN
IBN
REM1 00 0 03 03
Check the status of the posted line.
If the line status is
manual busy (ManB)
not ManB
Do
step 4
step 3
STA F S LTA TE RESULT
7213355 MB
Do
step 7
step 6