Nortel DMS-100 Series Replacement Procedures page 400

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-368 XPM card replacement procedures
NT2X57
in an RSC-S (DS-1) Model A RMM
9
At the MAP terminal
10
11
12
13
14
15
16
297-8021-547 Standard 14.02 May 2001
Use the following information to determine where to proceed.
If you entered this procedure
from
alarm clearing procedures
other
Test the RMM by typing
>TST
and pressing the Enter key.
If TST
passed
failed
Return the RMM to service by typing
>RTS
and pressing the Enter key.
If RTS
passed
failed
Send any faulty cards for repair according to local procedure.
Record the date the card was replaced, the serial number of the card, and the
symptoms that prompted replacement of the card. Go to step 16.
Return to the procedure that directed you to this procedure. At the point
where a faulty card list was produced, identify the next faulty card on the list,
and go to the appropriate card replacement procedure for that card in this
manual.
Obtain further assistance in replacing this card by contacting operating
company maintenance personnel.
You have successfully completed this procedure. Return to the maintenance
procedure that directed you to this card replacement procedure and continue
as directed.
(end)