Nortel DMS-100 Series Replacement Procedures page 326

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-294 XPM card replacement procedures
NT2X11
in an RSC-S (DS-1) Model A RMM
At the RMM shelf
7
8
297-8021-547 Standard 14.02 May 2001
CAUTION
Static discharge may cause damage to circuit packs
Put on a wrist strap and connect it to the frame of the RMM
before removing any cards. This protects the RMM against
service degradation caused by static electricity.
Put on a wrist strap.
Remove the NT2X11 card as shown in the following figures.
a
Locate the card to be removed on the appropriate shelf.
b
Open the locking levers on the card to be replaced and gently pull the
card toward you until it clears the shelf.
(continued)