At the MAP display
15
Test the links busied in step 12 by typing
>TST LINK link_no
and pressing the Enter key.
where
link_no
is one of two links associated with the replacement card
Note: Repeat this step for the other link associated with the replacement
card.
If test
failed
passed
16
Return to service the links busied in step 12 by typing
>RTS LINK link_no
and pressing the Enter key.
where
link_no
is one of two links associated with the replacement card
Note: Repeat this entry for the other link associated with the replacement
card.
If RTS
failed
passed
17
Determine if there are remaining links to clear.
If there are
remaining links to clear
no remaining links to clear
18
If you were directed to this procedure from another maintenance procedure,
return now to the procedure that directed you here and continue as directed;
otherwise, continue with step 19.
19
Determine if an ILCM unit is manual busy.
If ILCM unit
is ManB
DMS-100 Family NA100 Card Replacement Procedures Volume 4 of 7 LET0015 and up
XPM card replacement procedures
in an IOPAC HIE
Do
step 24
step16
Do
step 24
step17
Do
step 12
step18
Do
step 20
1-929
NT6X27
(continued)