Nortel DMS-100 Series Replacement Procedures page 155

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

Replacing an NT2X06 card in an RMM
At your current location
1
Obtain a replacement card. Ensure that the replacement card has the same
product equipment code (PEC), including suffix, as the card to be removed.
2
If you were directed to this procedure from another maintenance procedure,
go to step 8; otherwise, continue with step 3.
At the MAP display
3
Access the TTP level of the MAP and post the RMM that contains the card to
be replaced by typing
>MAPCI;MTC;TRKS;TTP;POST P RMM rmm_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf in which the card is to be replaced
Example of a MAP response:
LAST CIRCUIT = 27
POST CKT IDLED
SHORT CLLI IS:
OK, CLLI POSTED
POST
20
TTP 6–006
CKT TYPE
OG
MF RMM 0 0
4
Check the status of the RMM.
If
MB, PMB, RMB
other
5
Busy the trunks that are associated with the RMM to be busied by typing
>BSY ALL
and pressing the Enter key.
6
At the PM level of the MAP display, post the RMM by typing
>PM;POST RMM rmm_no
and pressing the Enter key.
where
DMS-100 Family NA100 Card Replacement Procedures Volume 4 of 7 LET0015 and up
XPM card replacement procedures
in an OPM RMM
OTDA00
DELQ
BUSY Q
PM NO.
COM LANG
OTWAON23DA00 2001
DIG
STA S R DOT TE R
LO
P_IDL
Do
step 8
step 5
1-123
NT2X06
(continued)