Nortel DMS-100 Series Replacement Procedures page 754

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-722 XPM card replacement procedures
NT6X17
in an RSC LCM
11
12
13
14
15
16
297-8021-547 Standard 14.02 May 2001
(end)
and pressing the Enter key.
If RTS
passed
failed
Send any faulty cards for repair according to local procedure.
Record the following items in office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card
Go to step 16.
Return to the Alarm Clearing Procedure that directed you to this card
replacement procedure. If necessary, go to the point where the faulty card list
was produced, identify the next faulty card on the list, and go to the
appropriate replacement procedure in this manual for that card.
Obtain further assistance in replacing this card by contacting personnel
responsible for a higher level of support.
You have successfully completed this procedure. Return to the maintenance
procedure that directed you to this card replacement procedure and continue
as directed.