Nortel DMS-100 Series Replacement Procedures page 149

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

At the RMM
6
Power down the unit by setting the ON/OFF switch on the power converter
faceplate to the OFF position. Both the CONVERTER FAIL LED and FRAME
FAIL LED on the modular supervisory panel (MSP) will be ON.
7
Replace the NT2X06 card using the common replacing a card procedure in
this document. When you have completed the procedure, return to this point
in the procedure.
8
Power up the RMM unit as follows:
Ensure the converter (NT2X06) is inserted. Set the POWER switch to the ON
position.
9
Press the RESET button on the power converter while setting the circuit
breaker on the MSP to the ON position. Both the CONVERTER FAIL LED
and FRAME FAIL lamp on the MSP will be ON.
If you were directed to this procedure from the Alarm Clearing Procedures ,
10
return now to the alarm clearing procedure that directed you here. Otherwise,
continue with step 11.
At the MAP terminal
11
Go to the PM level and post the RMM, if not already posted, and load the
RMM by typing
>PM;POST rmm_no;LOADPM
and pressing the Enter key
where
rmm_no
is the number of the RMM shelf where the card is to be replaced
If
message is loadfile
found in directory
load passed
load failed
DMS-100 Family NA100 Card Replacement Procedures Volume 4 of 7 LET0015 and up
XPM card replacement procedures
in an IOPAC RMM
DANGER
Static electricity damage
Wear a wrist strap connected to the wrist strap grounding
point at the top of each equipment rack, (Bay 0, 1, 2, and 3),
while handling circuit cards. This protects the cards against
damage caused by static electricity.
Do
step 12
not
step 29
step 32
1-117
NT2X06
(continued)