Nortel DMS-100 Series Replacement Procedures page 906

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-874 XPM card replacement procedures
NT6X21
in an OPM
(end)
6
At the OPM cabinet
7
At the MAP terminal
8
9
10
11
12
13
297-8021-547 Standard 14.02 May 2001
Busy the line by typing
>BSY
and pressing the Enter key.
Go to the common replacing a line card procedure in this document. When
you have completed the procedure, return to this point.
Test the line card just replaced by typing
>DIAG
and pressing the Enter key.
If the DIAG
passed
failed
Return the line card to service by typing
>RTS
and pressing the Enter key.
If RTS
passed
failed
Send any faulty cards for repair according to local procedure.
Record the following items in office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card
Go to step 13.
Obtain further assistance in replacing this card by contacting the personnel
responsible for higher level of support.
You have successfully completed this procedure.