Nortel DMS-100 Series Replacement Procedures page 486

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-454 XPM card replacement procedures
NT2X70
in an OPM HIE
68
69
70
71
72
73
74
297-8021-547 Standard 14.02 May 2001
(end)
Return the ESA processor to service by typing
>RTS
and pressing the Enter key.
If RTS
passed
failed
Send any faulty cards for repair according to local procedure.
Record the following items in office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card.
Go to step 74.
Return to the procedure that directed you to this card replacement procedure.
If necessary, go to the point where the faulty card list was produced, identify
the next faulty card on the list, and go to the appropriate replacement
procedure in this manual for that card.
Obtain further assistance in replacing this card by contacting personnel
responsible for higher level of support.
You have successfully completed this procedure. Return to the maintenance
procedure that directed you to this card replacement procedure and continue
as directed.