Nortel DMS-100 Series Replacement Procedures page 734

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-702 XPM card replacement procedures
NT4X98
in an RSC-S (PCM-30) Model B RMM
At the MAP terminal
12
13
14
15
16
17
18
19
20
297-8021-547 Standard 14.02 May 2001
Test the RMM by typing
>TST
and pressing the Enter key.
If TST
passed
failed
Return the RMM to service by typing
>RTS
and pressing the Enter key.
If RTS
passed
failed
Post the MTADRIVER by typing
>TRKS;TTP;POST P RMM rmm_no ckt_no
where
rmm_no
is the number of the RMM with the new MTADRIVER card
ckt_no
is the number of the new MTADRIVER card
and pressing the Enter key.
Return the MTADRIVER to service by typing
>BSY ALL;RTS ALL
and pressing the Enter key.
Send any faulty cards for repair according to local procedure.
Record the date the card was replaced, the serial number of the card, and the
symptoms that prompted replacement of the card. Go to step 20.
Return to the Alarm Clearing Procedures that directed you to this procedure.
At the point where a faulty card list was produced, identify the next faulty card
on the list, and go to the appropriate card replacement procedure for that card
in this manual.
Obtain further assistance in replacing this card by contacting operating
company maintenance personnel.
You have successfully completed this procedure. Return to the maintenance
procedure that directed you to this card replacement procedure and continue
as directed.
(end)
Do
step 13
step 18
Do
step 14
step 19