Nortel DMS-100 Series Replacement Procedures page 376

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-344 XPM card replacement procedures
NT2X57
in an OPM RMM
Replacing an NT2X57 card in an RMM
At the MAP display
1
2
At the RMM shelf
3
297-8021-547 Standard 14.02 May 2001
(continued)
Obtain a replacement card. Ensure that the replacement card has the same
product equipment code (PEC), including suffix, as the card to be removed.
Access the TTP level of the MAP and post the signal distribution circuits on
the card to be replaced by typing
>MAPCI;MTC;TRKS;TTP;POST P RMM rmm_no ckt_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf where the card is to be replaced
ckt_no
is the number of the first circuit where the NT2X57 card is physically
located.
Example of a MAP response:
LAST CIRCUIT = 14
POST CKT IDLED
SHORT CLLI IS:
OK, CLLI POSTED
POST
13
DELQ
TTP 6–006
CKT TYPE
PM NO.
OG TESTEQ RMM 0 0
WARNING
Static electricity damage
Wear a wrist strap connected to the wrist strap grounding
point of a frame supervisory panel (FSP) while handling
circuit cards. This protects the cards against damage caused
by static electricity.
Replace the NT2X57 card using the common replacing a card procedure in
this document. When you have completed the procedure, return to this point.