Nortel DMS-100 Series Replacement Procedures page 240

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-208 XPM card replacement procedures
NT2X09
in an RSC-S (DS-1) Model A RMM
10
11
12
13
At the MAP terminal
14
15
297-8021-547 Standard 14.02 May 2001
Use the following information to determine where to proceed.
If you entered this procedure
from
alarm clearing procedures
other
Power up the RMM unit in the following sequence:
a
Ensure the converter (NT2X09) is inserted. A major audible alarm may
sound. This alarm is silenced when power is restored to the converter.
b
Set the POWER switch to the ON position.
If FSP is equipped with
fuses
circuit breakers
Press and hold the RESET button for 1 s. Both the converter FAIL LED and
FRAME FAIL lamp on the FSP will be OFF. Go to step 14.
Press the RESET button while setting the circuit breaker to the ON position.
Both the converter FAIL LED and FRAME FAIL lamp on the FSP will be ON.
Reload the RMM by typing
>LOADPM
and pressing the Enter key.
If
message loadfile
found in directory is
received
load passes
load fails
Use the following information to determine where to proceed.
If system load module
version 1
version 2
(continued)
Do
step 23
step 11
Do
step 12
step 13
Do
step 15
not
step 19
step 24
Do
step 16
step 17