Nt2X10 In An Opm Rmm - Nortel DMS-100 Series Replacement Procedures

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-232 XPM card replacement procedures
NT2X10
in an OPM RMM
At the RMM shelf
4
At the MAP display
5
6
7
8
9
10
297-8021-547 Standard 14.02 May 2001
(end)
WARNING
Static electricity damage
Wear a wrist strap connected to the wrist strap grounding
point of a frame supervisory panel (FSP) while handling
circuit cards. This protects the cards against damage caused
by static electricity.
Replace the NT2X10 card using the common replacing a card procedure in
this document. When you have completed the procedure, return to this point.
Test the new NT2X10 card by typing
>TST
and pressing the Enter key.
If TST
passed
failed
Return to service the circuits busied in step 3 by typing
>RTS
and pressing the Enter key.
If RTS
passed
failed
Send any faulty cards for repair according to local procedure.
Record the following items in office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card
Go to step 10.
Obtain further assistance in replacing this card by contacting the personnel
responsible for higher level of support.
You have completed this procedure.
Do
step 6
step 9
Do
step 7
step 9