Nortel DMS-100 Series Replacement Procedures page 135

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

and pressing the Enter key.
If unit 0
RTS passed
RTS failed
39
Post the RMM that is controlled by the alarm and control card you have just
replaced by typing
>POST RMM rmm_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM to be posted, as recorded in step 5
40
Load the RMM by typing
>LOADPM
and pressing the Enter key.
41
Return the RMM to service by typing
>RTS
and pressing the Enter key.
If the rmm
RTS passed
RTS failed
42
Post the ESA processor that is controlled by the alarm and control card you
have just replaced by typing
>POST ESA esa_no
and pressing the Enter key.
where
esa_no
is the number of the ESA processor to be posted, as recorded in step 5
43
Load the ESA processor by typing
>LOADPM
and pressing the Enter key.
44
Return the ESA to service by typing
>RTS
DMS-100 Family NA100 Card Replacement Procedures Volume 4 of 7 LET0015 and up
XPM card replacement procedures
in an OPM
Do
step 39
step 47
Do
step 42
step 47
1-103
NT0X91AE
(continued)