Pn
Name
No.
506 Stop Selection
with Servo OFF
507 Stop Selection
with Main
Power Supply
OFF
508 Undervoltage
Alarm
Selection
509 Momentary
Hold Time
OMNUC G5-series (Pulse-train Input Type) AC Servomotors and Servo Drives User's Manual
Setting
Description
Set the stop operation to be performed when
the servo is OFF.
0
During deceleration: Dynamic brake
After stopping: Dynamic brake
Error counter: Clear
1
During deceleration: Free-run
After stopping: Dynamic brake
Error counter: Clear
2
During deceleration: Dynamic brake
After stopping: Servo-free
Error counter: Clear
3
During deceleration: Free-run
After stopping: Servo-free
Error counter: Clear
4
During deceleration: Dynamic brake
After stopping: Dynamic brake
Error counter: Hold
5
During deceleration: Free-run
After stopping: Dynamic brake
Error counter: Hold
6
During deceleration: Dynamic brake
After stopping: Servo-free
Error counter: Hold
7
During deceleration: Free-run
After stopping: Servo-free
Error counter: Hold
8
During deceleration: Emergency stop
After stopping: Dynamic brake
Error counter: Clear
9
During deceleration: Emergency stop
After stopping: Servo-free
Error counter: Clear
Set the stop operation to be performed when
the main power supply is turned OFF.
The set values for this parameter are the same
as those of Stop Selection with Servo OFF
(Pn506).
Select whether to allow an LV trip or turn OFF
the servo when a main power supply alarm
occurs.
Set the Main Power Supply Alarm detection
time.
Appendices
Default
Setting
Unit
setting
range
0
0 to 9
0
0 to 9
1
0 to 1
70
1 ms
70 to
2,000
Cycle the
power
supply
A
Required
A - 25