7 Parameter Details
Pn523
Torque Limit Switching Setting 1
Setting
0 to 4,000
range
• Set the rate of change when switching from No.1 Torque Limit to No.2 Torque Limit.
• When set to 0, switching takes place immediately.
Torque Limit
Switching (TLSEL)
No.1
Torque Limit
(Pn013)
No.2
Torque Limit
(Pn522)
Pn524
Torque Limit Switching Setting 2
Setting
0 to 4,000
range
• For this parameter, set the same value as for Torque Limit Switching Setting 1 (Pn523).
Pn525
Forward External Torque Limit
Setting
0 to 500
range
• Set the forward external torque limit for the torque limit switching input.
• The unit is 0.1% of the rated torque.
Pn526
Reverse External Torque Limit
Setting
0 to 500
range
• Set the reverse external torque limit for the torque limit switching input.
• The unit is 0.1% of the rated torque.
Pn527
Reserved
Setting
30
range
• Do not set.
7 - 52
Unit
ms/100%
Torque Limit
Switching Setting 1
(Pn523)
Unit
ms/100%
Unit
%
Unit
%
Unit
–
OMNUC G5-series (Pulse-train Input Type) AC Servomotors and Servo Drives User's Manual
Default
0
Cycle the
setting
power supply
Torque Limit Switching
Setting 2 (Pn524)
Default
0
Cycle the
setting
power supply
Default
500
Cycle the
setting
power supply
Default
500
Cycle the
setting
power supply
Default
30
Cycle the
setting
power supply
Position Speed
–
Position Speed
–
Position Speed
–
Position Speed
–
–