7 Parameter Details
Pn512
Overload Detection Level Setting
Setting
0 to 500
range
• Set the overload detection level.
• The value is regarded as 115% if set to 0.
• The value is regarded as 115% also if set to more than 115.
• The unit is a percentage (%) of the rated torque.
Pn513
Overspeed Detection Level Setting
Setting
0 to 20,000
range
• Set the overspeed detection level.
• The overspeed detection level is 1.2 times the maximum rotation speed of the Servomotor if set to 0.
• This parameter should normally be set to 0. The setting should be changed only when it is necessary
to lower the overspeed detection level.
• The set value of this parameter is limited to 1.2 times the maximum rotation speed of the Servomotor.
• The detection margin of error for the set value is ±36 r/min for a 5-core incremental encoder.
Pn514
Overrun Limit Setting
Setting
0 to 1,000
range
• Set the allowable operating range for the position command input range.
• If the set value is exceeded, an Overrun Limit Error will occur.
Without position command input
Servomotor
With position command input
Servomotor
7 - 48
Unit
Unit
Unit
0.1 rotation
Load
Pn514 Pn514
Servomotor
operating
range
Alarm generation range
Position command
Pn514
Alarm generation range
Servomotor operating range
OMNUC G5-series (Pulse-train Input Type) AC Servomotors and Servo Drives User's Manual
%
Default
setting
r/min
Default
setting
Default
setting
Alarm generation range
Load
input range
Pn514
Alarm generation
range
All
0
Cycle the
power supply
All
0
Cycle the
power supply
Position
10
Cycle the
power supply