7 Parameter Details
Pn610
Function Expansion Setting
Setting
0 to 63
range
• Enable or disable the extended function allocated to each bit.
Bit
bit 0
Instantaneous speed observer function
bit 1
Disturbance observer function
bit 2
Disturbance observer operation setting
bit 3
Inertia ratio switching function
bit 4
Electric current response improvement
function
bit 5
Disabled
Set the decimal value that is converted from the bit values.
[Example]
Instantaneous speed observer function: Enabled
Disturbance observer function: Enabled
Disturbance observer operation setting: Always enabled
Inertia ratio switching function: Disabled
Electric current response improvement function: Enabled
With the above settings, the value in each bit is expressed as 10011, which is 19 in decimal.
Therefore, set the parameter to 19.
Pn611
Electric Current Response Setting
Setting
50 to 100
range
• Make fine adjustment to electric current response. The default setting is 100
Pn613
Inertia Ratio 2
Setting
0 to 10,000
range
• Set the second load inertia as a percentage of the motor rotor inertia.
7 - 56
Unit
Function
Unit
%
Unit
OMNUC G5-series (Pulse-train Input Type) AC Servomotors and Servo Drives User's Manual
Default
0
Cycle the
setting
power supply
Set value
0
Disabled
Disabled
Always enabled
Only when Gain 1 is
Disabled
Disabled
Default
100
Cycle the
setting
power supply
.
%
Default
250
Cycle the
setting
power supply
Position
1
Enabled
Enabled
selected
Enabled
Enabled
All
All