Sigma II User's Manual
5.5.2
Using the Servo ON Input Signal
The basic use and wiring procedure for the Servo ON (/S-ON) input signal
(sequence input signal) is described below. Use this signal to forcibly turn OFF the
servomotor from the host controller.
ð Input /S-ON CN1-40
This signal is used to turn the servomotor ON and OFF.
CN1-40
State
ON
OFF
• Do not use the Servo ON (/S-ON) signal to start or stop the motor. Always use an input reference sig-
nal, such as Speed Reference to start or stop the servomotor.
Doing so will shorten the life of the servo amplifier.
Set the following parameter to 7 if the /S-ON signal will not be used.
Parameter
Pn50A.1
/S-ON Signal Mapping
I/O power supply
+24V
+24V
Host controller
/S-OUT
0V
Servo ON
Status
Turns ON the servomotor: operates
Closed or low level
according to signal input.
This is the default state.
Servomotor cannot operate.
Open or high level
Do not turn OFF the servomotor while it
is operating except in an emergency.
CAUTION
!
Signal
Default Setting: 0
5-71
Chapter 5: Parameter Settings and Functions
Servo amplifier
3.3kΩ
Photo
IN
CN1-47
coupler
7mA
CN1-40
Speed/Torque Control,
Position Control
Result
Setting
Description
Speed/Torque Control,
Position Control