Mechanical Operating Conditions; Electrical Operating Conditions; Installation Conditions - YASKAWA MP3000 Series Setup Manual

Machine controller system
Hide thumbs Also See for MP3000 Series:
Table of Contents

Advertisement

A.2.2

Mechanical Operating Conditions

Item
Vibration Resistance
Shock Resistance
A.2.3

Electrical Operating Conditions

Item
Noise Resistance
A.2.4

Installation Conditions

Item
Ground
Cooling Method
Conforms to JIS B 3502.
• Continuous Vibration:
Frequency: 5 to 8.4 Hz, Single amplitude: 1.75 mm,
Frequency: 8.4 to 150 Hz, Fixed acceleration: 4.9 mm/s
• Intermittent Vibration:
Frequency: 5 to 8.4 Hz, Single amplitude: 3.5 mm
Frequency: 8.4 to 150 Hz, Fixed acceleration: 9.8 mm/s
10 sweeps each in X, Y, and Z directions for both intermittent and continuous
vibration
Size of shock: Peak acceleration of 147 m/s
Duration: 11 ms
3 times each in X, Y, and Z directions
Conforms to EN 61000-6-2 and EN 55011 (Group 1 Class A).
Power supply noise (FT noise): ±2 kV min. for one minute
Radiation noise (FT noise): ±1 kV min. for one minute
Ground noise (impulse noise): ±1 kV min. for 10 minutes
Electrostatic noise (contact discharge method): ±6 kV or more, 10 times
Specification
Ground to 100 Ω max.
Natural cooling or forced-air cooling
A.2 MP3300 Installation and Usage Conditions
A.2.2 Mechanical Operating Conditions
Specification
2
(15 G)
Specification
2
2
A-7
AppA