A.1 MP3200 Installation and Usage Conditions
A.1.3 Electrical Operating Conditions
A.1.3

Electrical Operating Conditions

Noise Resistance
A.1.4

Installation Conditions

Ground
Cooling Method
A-4
Item
Conforms to EN 61000-6-2 and EN 55011 (Group 1 Class A).
Power supply noise (FT noise): ±2 kV min. for 1 minute
Radiation noise (FT noise): ±1 kV min., for 1 minute
Ground noise (impulse noise): ±1 kV min., for 10 minutes
Electrostatic noise (conducted): ±4 kV min., 10 times
Item
Ground to 100 Ω max.
Natural cooling or forced cooling
Specification
Specification