Specifying Sequence Programs
Sequence programs must be specified directly. Indirect designations cannot be used.
Specify the program number of the sequence program to execute (SPM).
M-EXECUTOR Program Execution Definitions
Work Registers
Work registers are used to monitor sequence programs.
The work registers have Status Flags inside the M-EXECUTOR control registers, in the same
way as motion programs that are registered in the M-EXECUTOR.
 Sequence Program Status Flags
The Sequence Program Status Flags give the execution condition of the sequence program.
The following table describes the meanings of the Status Flags.
Bit No.
0
Program is being executed.
1
Reserved for system.
2
Reserved for system.
3
Reserved for system.
4
Reserved for system.
5
Reserved for system.
6
Reserved for system.
7
Reserved for system.
8
There is a program alarm.
9
Execution is stopped at a breakpoint.
A
Reserved for system.
B
The program is in Debug Mode (EWS debugging).
C
Program Type, 1: Sequence program
D
Start Request History
E
Reserved for system.
F
Reserved for system.
Sequence Program Alarms
If an error is detected when a sequence subprogram is called with an SSEE instruction, bit 8
(Program Alarm) turns ON. When the error is removed, this bit turns OFF.
Note
The following errors can occur.
• The called program is not registered.
• The called program is not a sequence program.
• The called program is not a subprogram (a main program was called).
• Called Program Number Limit Exceeded Error
• Too Many Nesting Levels Error
4.1 User Program Types and Execution Timing
Status
4.1.3 Sequence Programs
Sequence Program
SPM001
IF MW000<32767;
MW000=MW000+1;
ELSE;
MW000;
IEND;
4-25