Monitored Data - ABB RELION Series Communication Protocol Manual

Grid automation dnp3 communication protocol manual
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
DNP3 parameters
Parameter
Default Var Obj 32
Default Var Obj 40
Default Var Obj 42
4.2
30
Values (Range)
Unit
1=1:32bit AI evt
2=2:16bit AI evt
3=3:32bit AI
evt&time
4=4:16bit AI
evt&time
5=5: float AI evt
6=6:double AI evt
7=7:float AI
evt&time
8=8:double AI
evt&time
1=1:32bit AO
2=2:16bit AO
3=3:AO float
4=4:AO double
1=1:32bit AO evt
2=2:16bit AO evt
3=3:32bit AO
evt&time
4=4:16bit AO
evt&time
5=5:float AO evt
6=6:double AO evt
7=7:float AO
evt&time
8=8:double AO
evt&time

Monitored data

Table 5:
DNP3
Parameter
Received frames
Transmitted frames
Physical errors
Link errors
Transport errors
Mapping errors
Status
Reset counters
Step
Default
7=7:float AI
evt&time
2=2:16bit AO
4=4:16bit AO
evt&time
Values (range)
Description
-1...2147483646
Total amount of received DNP3 frames
-1...2147483646
Total amount of transmitted DNP3 frames
-1...2147483646
Total amount of Physical layer errors noticed
-1...2147483646
Total amount of Link layer errors noticed
-1...2147483646
Total amount of Transport layer errors noticed
-1...2147483646
Total amount of Protocol mapping errors noticed
True, False
Status of communication
True, False
True = Reset all diagnostic counters
1MRS758757 A
Description
1=32 bit AI event; 2=16 bit AI event; 3=32
bit AI event with time; 4=16 bit AI event
with time; 5=float AI event; 6=double AI
event; 7=float AI event with time;
8=double AI event with time.
1=32 bit AO; 2=16 bit AO; 3=AO float;
4=AO double.
1=32 bit AO event; 2=16 bit AO event;
3=32 bit AO event with time; 4=16 bit AO
event with time; 5=float AO event;
6=double AO event; 7=float AO event with
time; 8=double AO event with time.
REC615 and RER615
Communication Protocol Manual