Monitored Data - ABB 615 Series ANSI Manual

Modbus communication protocol
Hide thumbs Also See for 615 Series ANSI:
Table of Contents

Advertisement

1MAC052634-MB D
4.2
615/620 series ANSI
Communication Protocol Manual

Monitored data

The Modbus serial monitored data can be accessed with PST or via the LHMI path
Monitoring > Communication > Modbus > Serial.
Table 36:
Modbus serial
Parameter
Values (range)
1
0...2147483648
Received frames N
Transmitted frames N
0...2147483648
Cksm Err N
0...2147483648
Transmitted Exec A N
0...2147483648
Transmitted Exec B N
0...2147483648
Status N
True, False
1. N = instance number 1, 2...
The Modbus Ethernet monitored data can be accessed with PST or via the LHMI path
Monitoring > Communication > Modbus > Ethernet.
Table 37:
Modbus TCP/IP
Parameter
Values (range)
1
0...2147483648
Received frames N
Transmitted frames N
0...2147483648
Transmitted Exec A N
0...2147483648
Transmitted Exec B N
0...2147483648
Cn Rejects No socket
0...2147483648
Cn Rejects Not reg
0...2147483648
Status N
True, False
1. N = instance number 1, 2...
Modbus parameters and diagnostics
Description
Received Modbus frames by instance N
Transmitted Modbus frames by instance N
Checksum errors detected by instance N
Transmitted exception responses 1 and 2 by instance N
Transmitted exception responses 3 by instance N
Status of communication, instance N
Reset of diagnostic counters instance N
Description
Received Modbus frames by instance N
Transmitted Modbus frames by instance N
Transmitted exception responses 1 and 2 by instance N
Transmitted exception responses 3 by instance N.
Connection rejections due to no free sockets
Connection rejections due to not registered client IP.
Status of communication, instance N
Reset of diagnostic counters instance N
Section 4
49