Object 30 - Analog Inputs (Primary Readings)

Read with Object 30, Var 4, and Qualifiers 0, 1, 2, or 6. (Included in Class 0
responses.)
NOTE: Multipliers for Volts, Amps, and Power points are per user setup options.
Object
Point
Var
30
0
4
Meter Health
30
1
4
Volts A-N
30
2
4
Volts B-N
30
3
4
Volts C-N
30
4
4
Volts A-B
30
5
4
Volts B-C
30
6
4
Volts C-A
30
7
4
Amps A
30
8
4
Amps B
30
9
4
Amps C
30
10
4
Watts, 3-Ph
total
30
11
4
VARs, 3-Ph
total
30
12
4
VAs, 3-Ph total
30
13
4
Power Factor,
3-Ph total
30
14
4
Frequency
30
15
4
Positive Watts,
3-Ph,
Maximum Avg
Demand
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Description
Format
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
C: DNP Mapping
Range
Multiplier
0 or 1
N/A
0 to 32767
1, 10, or 100
0 to 32767
1, 10, or 100
0 to 32767
1, 10, or 100
0 to 32767
1, 10, or 100
0 to 32767
1, 10, or 100
0 to 32767
1, 10, or 100
0 to 32767
1 or 10
0 to 32767
1 or 10
0 to 32767
1 or 10
-32768 to
1, 10, 100 or
+32767
1000
-32768 to
1, 10, 100 or
+32767
1000
0 to +32767
1, 10, 100 or
1000
-1000 to
0.001
+1000
0 to 9999
0.01
-32768 to
1, 10, 100, or
+32767
1000
#
Doc
E149701
Units
Comments
None
0 = OK
V
Point value
= Actual
Volts/divisor
V
V
V
V
V
A
Point value
= Actual
Amps/divisor
A
A
W
Point value
= Actual
kWatts/divi-
sor
VAR
VA
None
Hz
W
C-13