Binary Output States - Electro Industries Shark 200 Installation & Operation Manual

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

Object 10 - Binary Output States
Read with Object 10, Var 2, and Qualifiers 0, 1, 2 or 6. (Included in Class 0
responses.)
Object
Point
Var
10
0
2
Reset Energy
Counters
10
1
2
Change to
Modbus RTU
Protocol
10
2
2
Reset Demand
Counters (Max
/ Min )
10
3
2
Read Relay 1
State RO1S
Relay 1
(expansion
port 1)
10
4
2
Read Relay 2
State RO1S
Relay 2
(expansion
port 1)
10
5
2
Read Relay 3
State RO1S
Relay 1
(expansion
port 2)
10
6
2
Read Relay 4
State RO1S
Relay 2
(expansion
port 2)
Supported Flags:
Bit 0: ONLINE (0=Offline, 1=Online) (If the Input is not present it will be shown as
Offline.)
Bit 1: RESTART (1=The Object is in the Initial State and has not been updated since
Restart.)
Bit 7: STATE (0=Off, 1=On)
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Description
Format
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
C: DNP Mapping
Range
Multiplier
Units
Always 1
N/A
None
Always 1
N/A
None
Always 1
N/A
None
Bit Flags
N/A
None
Bit Flags
N/A
None
Bit Flags
N/A
None
Bit Flags
N/A
None
#
Doc
E149701
Comments
Returns the Status and
State of the Relay in
the Flags.
Returns the Status and
State of the Relay in
the Flags.
Returns the Status and
State of the Relay in
the Flags.
Returns the Status and
State of the Relay in
the Flags.