Object 30 - Analog Inputs (Secondary Readings) - Electro Industries Shark 200 Installation & Operation Manual

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

Object 30 - Analog Inputs (Secondary Readings)

Read with Object 30, Var 4, and Qualifiers 0, 1, 2, or 6. (Included in Class 0
responses.)
NOTE: Object 30 may be either primary or secondary readings per a user setup
option. See page C-13 for the primary version of Object 30.
Object
Point
Var
30
0
4
Meter Health
30
1
4
Volts A-N
30
2
4
Volts B-N
30
3
4
Volts C-N
30
4
4
Volts A-B
30
5
4
Volts B-C
30
6
4
Volts C-A
30
7
4
Amps A
30
8
4
Amps B
30
9
4
Amps C
30
10
4
Watts, 3-Ph
total
30
11
4
VARs, 3-Ph
total
30
12
4
VAs, 3-Ph total
30
13
4
Power Factor,
3-Ph total
30
14
4
Frequency
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Description
Format
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
C: DNP Mapping
Range
Multiplier
0 or 1
N/A
0 to 32767
(150 / 32768)
0 to 32767
(150 / 32768)
0 to 32767
(150 / 32768)
0 to 32767
(300 / 32768)
0 to 32767
(300 / 32768)
0 to 32767
(300 / 32768)
0 to 32767
(10 / 32768)
0 to 32767
(10 / 32768)
0 to 32767
(10 / 32768)
-32768 to
(4500 /
+32767
32768)
-32768 to
(4500 /
+32767
32768)
0 to +32767
(4500 /
32768)
-1000 to
0.001
+1000
0 to 9999
0.01
#
Doc
E149701
Units
Comments
None
0 = OK
V
Values above
150V
secondary
read 32767.
V
V
V
Values above
300V
secondary
read 32767.
V
V
A
Values above
10A
secondary
read 32767.
A
A
W
VAR
VA
None
Hz
C-10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Shark 200t

Table of Contents