The general specifications are as follows:
Operating temperature:
Storage temperature:
Relative air humidity:
EMC - Immunity interference:
Weight:
Dimensions (inch) W x H x L:
External connection:

7.5.2: Default Configuration:

The Shark® 200 meter automatically recognizes the installed Option card during
power up. If you have not programmed a configuration for the card, the unit defaults
to the following outputs:
Channel 1
Channel 2
Channel 3
Channel 4
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
7: Using the I/O Option Cards
(-20 to +70) °C
(-40 to +80) °C
Maximum 95%, non-condensing
EN61000-4-2
1.6 oz
0.72 x 2.68 x 3.26
AWG 12-26/(0.129 - 3.31) mm
5 pin, 0.200" pluggable terminal block
+Watts, +1800 Watts => 20 mA
-Watts,
-1800 Watts =>
0 Watts => 12 mA
+VARs, +1800 VARs => 20 mA
- VARs, -1800 VARs =>
0 VARs => 12 mA
Phase A Voltage WYE, 300 Volts => 20 mA
0 Volts => 4 mA
Phase A Voltage Delta, 600 Volts => 20 mA
Phase A Current, 10 A => 20 mA
0 Phase A Current, 0 A => 4 mA
#
Doc
E149701
2
4 mA
4 mA
7-8