E.8: Error Codes
The following table lists possible Error codes you will see if there is a problem upload-
ing a .CID file, along with the meaning of the code and the action required to correct
the error.
Code
20561
21325
16969
18766
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Name
BADPASS
TOOSMALL
TOOBIG
INVALID
E: Using the IEC61850 Network Card
Description
The Upload pass-
word is incorrect.
The uploaded file is
too small: it does
not contain the min-
imum necessary
description.
The uploaded file is
too big: it does not
fit in the reserved
area for the CID file.
The .CID file is not a
valid xml file, or it is
not UTF-8 encoded.
#
Doc
E149701
Required Action
Use the correct
password: check
product documenta-
tion for the correct
password.
Check to ensure the
file is not trimmed.
Sometimes an ille-
gal character (non-
ASCII) makes the
file look smaller.
Verify that the
entire file can be
read.
Check to ensure the
file is correct. Try to
delete large com-
ment sections or
historical sections.
Sometimes second-
ary IED descrip-
tions are in the
same file - delete
those from the file,
and leave just the
ones necessary to
configure the
INP300.
The .CID file is a
text file that needs
to begin with
"<?xml". Check to
ensure that the cod-
ification of the text
file is UTF-8; Multi-
byte codification will
also cause this
error.
E-30

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Shark 200t