Control Relay Outputs - Electro Industries Shark 200 Installation & Operation Manual

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

Object 12 - Control Relay Outputs
(Responds to Function 3 - Select, 4 - Operate, or 5 - Direct Operate; Count of 1 Only.)
(Control code 3 or 4, Qualifiers 17x or 28x, On - 0 msec; Off - 1 msec.)
(Only one control object at a time may be specified.)
Object
Point
Var
12
0
1
Reset Energy
Counters
12
1
1
Change to
Modbus RTU
Protocol
12
2
1
Reset Demand
Counters (Max
/ Min)
12
3
1
Control Relay
1 RO1S Relay
1 (expansion
port 1)
12
4
1
Control Relay
2 RO1S Relay
2 (expansion
port 1)
12
5
1
Control Relay
3 RO1S Relay
1 (expansion
port 2)
12
6
1
Control Relay
4 RO1S Relay
2 (expansion
port 2)
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Description
Format
N/A
N/A
N/A
N/A
N/A
N/A
N/A
C: DNP Mapping
Range
Multiplier
Units
N/A
N/A
none
N/A
N/A
none
N/A
N/A
none
N/A
N/A
none
N/A
N/A
none
N/A
N/A
none
N/A
N/A
none
#
Doc
E149701
Comments
Control Code 3 only
Responds to Function 6
(Direct Operate - No
Ack), Qualifier Code
17x, Control Code 3,
Count 0, On 0 msec, Off
1 msec ONLY.
Control Code 3 only
See Section C.4 for
operation rules and
parameters.
See Section C.4 for
operation rules and
parameters.
See Section C.4 for
operation rules and
parameters.
See Section C.4 for
operation rules and
parameters.
C-8