Electro Industries Shark 200 Installation & Operation Manual page 242

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

B.5.8: PQ Event Log Retrieval
The following is a detailed breakdown of the PQ Event Record byte-map (see page B-
39):
SIZE
6 bytes
2 bytes
2 bytes
1 byte
1 byte
2 bytes
18 bytes
12 bytes
14 bytes
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
PQ Event Record Definition 1
CONTENT
Timestamp
Present States
Event Channels
Capture Number
Flags
Event Cycle Tag
Worst Excursion RMS
Sample Calibrations
not used
B: Modbus Map and Retrieving Logs
NOTES
Timestamp of the
record
Bit mapped per trigger
events. 0 indicates an
untriggered state.
Bit mapped per trigger
events. 1 indicates a
channel changed state
and that the change to
the present state
caused the event.
0 if cycle was not cap-
tured, 1-255 if all or
part of the cycle was
captured
Always 0
Tag of the last sample
in the event cycle
For events ending a
surge or sag episode
(e.g. return to nor-
mal), RMS of the
channel is the worst
excursion (highest
surge, lowest sag) for
the episode. 0 for
other channels. Same
units as Waveform
Records
Same as sample cali-
brations in waveform
log non-sample cap-
ture summary
Always 0
#
Doc
E149701
OFFSET
0
6
8
10
11
12
14
32
44
B-58

Hide quick links: