* Setting the interval to EOI causes a record to be logged whenever an EOI pulse
event is generated. This is most commonly used in conjunction with the Digital
I/O Option Cards.
NOTE: The interval between records will not be even (fixed), and thus should not
be used with programs that expect a fixed interval.

Register List:

Registers:
Size:
The Register List controls what Modbus Registers are recorded in each record of the
Historical Log. Since many items, such as Voltage, Energy, etc., take up more than 1
register, multiple registers need to be listed to record those items.
For example: Registers 0x03E7 and 0x03E8 are programmed to be recorded by the
historical log. These registers program the log to record "Primary Readings Volts A-N."
• Each unused register item should be set to 0x0000 or 0xFFFF to indicate that it
should be ignored.
• The actual size of the record, and the number of items in the register list which are
used, is determined by the # registers in the header.
• Each register item is the Modbus Address in the range of 0x0000 to 0xFFFF.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
B: Modbus Map and Retrieving Logs
1 minute
3 minute
5 minute
10 minute
15 minute
30 minute
60 minute
End of Interval (EOI) Pulse*
0x7919 - 0x798D
1 register per list item, 117 list items
#
Doc
E149701
B-8