Waveform Log Record; Pq Event Record; Present States - Electro Industries Shark 200 Installation & Operation Manual

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

Waveform Log Record:

Byte
0
1
2
Value
Timestamp
Size: 970 bytes
Data: Each waveform record is 970 bytes, which contains the timestamp, the capture
number it is associated with (all 26 will have the same capture #), its own record
number (numbered 0-25) and the payload.
NOTE: The waveform records must be in sequential order. Verify that the record
numbers are sequential, and if they are not, the retrieval of that capture must be
restarted.

PQ Event Record:

Byte
0
1 2 3 4 5 6
Value
Timestamp
Pres-
ent
States
Size: 58 bytes
Data: See the first table in the PQ Event Log Retrieval section for detailed information
about the data.
NOTE: The "not used" section of the PQ Event record byte-map is simply 0.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
3
4
5
6
Capture #
7
8
9
10
11
Event
Cap-
Flags
Chan-
ture
nels
#
B: Modbus Map and Retrieving Logs
7
8
Record #
Record Payload
12
13
14
...
31
Event Cycle
Worst
Tag
Excursion RMS
#
Doc
E149701
-
-
969
32
...
43
44
...
Sample
Not Used
Calibrations
(0X0)
57
B-39