NOTES:
• The value for A is a product of the Ct-n value and the Ct-S value.
• Ct-n and Ct-S are dictated by primary current; Ct-d is secondary current.
MENU
ENTER
-
A
-
B
-
C
Press Enter

6.2.5.3: Configuring PT Setting

The PT Setting has three parts: Pt-n (numerator), Pt-d (denominator), and Pt-S (scal-
ing).
1. Press the Enter button when Pt is in the A window. The PT-n screen appears. You
can either:
• Change the value for the PT numerator.
• Access one of the other PT screens by pressing the Enter button: press Enter
once to access the Pt-d screen, twice to access the Pt-S screen.
a. To change the value for the PT numerator or denominator:
From the Pt-n or Pt-d screen:
• Use the Down button to select the number value for a digit.
• Use the Right button to move to the next digit.
b. To change the value for the PT scaling:
From the Pt-S screen, use the Right button or the Down button to choose the
scaling you want. The Pt-S setting can be 1, 10, 100, or 1000.
NOTE: If you are prompted to enter a password, refer to Section 6.2.4 for instruc-
tions on doing so.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
MENU
ENTER
-
A
-
B
-
C
Use buttons to set Ct-n
6: Using the Shark® 200 Meter
MENU
ENTER
-
A
-
B
-
C
Ct-d cannot be changed
#
Doc
E149701
MENU
ENTER
-
A
-
B
-
C
Use buttons to select
scaling
6-11