2.1.1: Voltage and Current Inputs

Universal Voltage Inputs

Voltage inputs allow measurement up to Nominal 576 V AC (Phase to Reference) and
721 V AC (Phase to Phase). The unit will perform to specification when directly
connected to 69 volt, 120 volt, 230 volt, 277 volt, and 347 volt power systems.
NOTE: Higher Voltages require the use of potential transformers (PTs).

Current Inputs

The unit supports a 5 A or a 1 A secondary for current measurements.
NOTE: The secondary current must be specified and ordered with the meter.
The current inputs are only to be connected to external current transformers.
The Shark® 200 meter's current inputs use a unique dual input method:
Method 1: CT Pass Through:
The CT wire passes directly through the meter without any physical termination on
the meter. This is preferable for utility users when sharing relay class CTs.
Method 2: Current "Gills":
This unit additionally provides ultra-rugged termination pass through bars that allow
CT leads to be terminated on the meter. This, too, eliminates any possible point of
failure at the meter. This is a preferred technique for insuring that relay class CT
integrity is not compromised (the CT will not open in a fault condition).

2.1.2: Ordering Information

Shark200 - 60 - 10- V2- D -INP100S - X
1
1. Model:
Shark® 200 Meter/Transducer
Shark® 200T Transducer (no display)
2. Frequency:
50: 50 Hz System
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
2
3
4
5
#
Doc
2: Meter Overview and Specifications
6
7
E149701
2-5