2.4: Accuracy

(For full Range specifications see 2.2: Specifications on page 2-12.)
Shark 200 Clock Accuracy:
o
For 23
C, 3 Phase balanced Wye or Delta load, at 50 or 60 Hz (as per order), 5 A
(Class 10) nominal unit, accuracy as follows:
Parameter
Voltage L-N [V]
Voltage L-L [V]
Current Phase [A]
Current Neutral (calcu-
lated) [A]
Active Power Total [W]
Active Energy Total [Wh]
Reactive Power Total
[VAR]
Reactive Energy Total
[VARh]
Apparent Power Total
[VA]
Apparent Energy Total
[VAh]
Power Factor
Frequency [Hz]
Total Harmonic Distortion
[%]
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Max. +/-2 seconds per day at 25
Table 2:
Accuracy
0.1% of reading
2
0.2% of reading
1, 3
0.1% of reading
1
2% of Full Scale
1, 2
0.2% of reading
1, 2
0.2% of reading
1, 2
0.2% of reading
1, 2
0.2% of reading
1, 2
0.2% of reading
1, 2
0.2% of reading
1, 2
0.2% of reading
+/- 0.007 Hz
1, 4
+/- 2%
#
Doc
E149701
2: Meter Overview and Specifications
Accuracy Input Range1
(69 to 480) V
(120 to 600) V
(0.15 to 5) A
(0.15 to 5) A @ (45 to 65)
Hz
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
(0.15 to 5) A @ (69 to
480) V @ +/- (0 to 0.8)
lag/lead PF
(0.15 to 5) A @ (69 to
480) V @ +/- (0 to 0.8)
lag/lead PF
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
(45 to 65) Hz
(0.5 to 10) A or (69 to
480) V, measurement
range (1 to 99.99)%
o
C
2-19