Shark® ST40 Meter Quickstart Guide
CAUTION! Installation of the Shark® ST40 meter must be performed only by qualified
personnel who follow standard safety precautions during all procedures. Those personnel should
have appropriate training and experience with high voltage devices. Appropriate safety gloves,
safety glasses and protective clothing are recommended.
During normal operation of the ST40 meter, dangerous voltages flow through many parts of the unit, includ-
ing: Terminals and any connected CTs (Current Transformers) and PTs (Potential Transformers), all I/O
Modules and their circuits. All Primary and Secondary circuits can, at times, produce lethal voltages and
currents. Avoid contact with any current-carrying surfaces.
Do not use the meter or any I/O device for primary protection or in an energy-limiting capacity. The meter can
only be used as secondary protection.
IMPORTANT! Refer to your meter's Installation and Operation Manual for additional safety warnings before
performing installation, wiring, or maintenance of your meter. See the link to the manual, below.
NOTE: This Quickstart Guide gives basic installation, wiring, and programming instructions.For additional
meter operation and programming information, refer to your meter's Installation and Operation Manual and
the Communicator PQA
TM
User Manual:
https://www.electroind.com/products/st40/
From the webpage, click Technical Documents>User Manual.
Software Manual:
https://www.electroind.com/products/communicatorpqa-software-application-5/
From the webpage, click Technical Documents>User Manual.
CommunicatorPQA
Setup Software:
TM
https://www.electroind.com/products/communicatorpqa-software-application-5/
From the webpage, click Download ComPQA Pro. To get a Professional license for the software, email
sales@electroind.com or call 516-334-0870.
All EIG's metering and software products' literature can be accessed from:
https://www.electroind.com/all-products/
For software and metering integration, EIG's Technical Support Engineers are available on an hourly or daily
basis to help with typical commissioning assistance, which includes:
Verifying meter installation and wiring.
Verifying proper system integration.
Working with 3rd parties to ensure cross compatibility.
Advising users on best practices for optimal implementation.
You can reach Technical Support from 8 a.m. to 8 p.m. EST, Monday-Friday, at 516-334-0870.
Electro Industries/GaugeTech
Powered by Innovation™
, MeterManagerPQA
, and EnergyPQA.com
TM
Software User Manual on EIG's website:
TM
#
Doc
E183703
®
Shark
ST40 Meter Quickstart
V.1.01
QS - 1

Advertisement

loading

Summary of Contents for Electro Industries Shark ST40

  • Page 1 Working with 3rd parties to ensure cross compatibility. • Advising users on best practices for optimal implementation. You can reach Technical Support from 8 a.m. to 8 p.m. EST, Monday-Friday, at 516-334-0870. Electro Industries/GaugeTech ™ E183703 V.1.01 QS - 1...
  • Page 2: Mechanical Installation

    240 V corner grounded. WYE/Delta WYE/Delta 4-wire 4-wire No PTs, 3 PTs 3 CTs 3 CTs Delta Delta 3-wire 3-wire 2 PTs No PTs 2 CTs 2 CTs Electro Industries/GaugeTech ™ E183703 V.1.01 QS - 2 Powered by Innovation™...
  • Page 3 9.Press the ENTER button to go to the PT Scaling setting screen (PT-S). The current Scaling is shown in the second line. Press the DOWN ARROW to choose another value. You can choose 1, 10, 100, or 1000. NOTE: See example CT and PT Settings beginning on page QS-5. Electro Industries/GaugeTech ™ E183703 V.1.01 QS - 3 Powered by Innovation™...
  • Page 4 You will see the confirmation screen (Stor ALL done) and then the meter resets. NOTE: If you do not want to save your settings, press the RIGHT ARROW. YES changes to no. Press the ENTER button. Electro Industries/GaugeTech ™ E183703 V.1.01 QS - 4 Powered by Innovation™...
  • Page 5 Once you make a physical connection between the meter and your PC, you can connect to the soft- ware. 1.Open CommunicatorPQA software (see page QS-1 for download link). 2. Click Connect in the Icon Bar. Electro Industries/GaugeTech ™ E183703 V.1.01 QS - 5...
  • Page 6 - Primary (CT Numerator): 1 - 9999 - Secondary (CT Denominator): 5 or b. PT Ratio, enter: - Primary (PT Numerator): 1 - 9999 - Secondary (PT Denominator): 1 - 9999 Electro Industries/GaugeTech ™ E183703 V.1.01 QS - 6 Powered by Innovation™...
  • Page 7 PC Time to set the time using your PC’s time. 3. Click Send. NOTE: The meter offers multiple Time Synchronization methods. See Chapter 30, Section 30.1.3 in the software manual (see page QS-1.) Electro Industries/GaugeTech ™ E183703 V.1.01 QS - 7...
  • Page 8 Save Profile at the bottom left of the Device Profile screen, to send the new settings to the meter. The meter will reboot and then you can reconnect to it. Shark® is a registered trademark of Electro Industries/GaugeTech (EIG). CommunicatorPQA , MeterManagerPQA , and EnergyPQA.com...