D.4.1.3: 32-Bit Binary Counter Without Flag (Obj. 20, Var. 5)

Counters support the following functions:
Read (Function 1)
A READ request for Variation 0 is responded to with Variation 5.
Counters are used to communicate the following data measured by Shark® 100S
meters:
Hour Readings
Hour Readings (Points 0 - 4)
NOTE: These readings may be cleared by using the Control Relay Output Block (see
previous Section D.4.1.2).

D.4.1.4: 16-Bit Analog Input Without Flag (Obj. 30, Var. 4)

Analog Inputs support the following functions:
Read (Function 1)
A READ request for Variation 0 is responded to with Variation 4.
Analog Inputs are used to communicate the following data measured by Shark® 100S
meters:
• Health Check
• Phase-to-Neutral Voltage
• Phase-to-Phase Voltage
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Point
Readings
0
+W hour
1
-W hour
2
+VAR hour
3
-VAR hour
4
+VA hour
Doc
D: DNP 3.0 Protocol Assignments
Unit
Wh
Wh
VARh
VARh
VAh
E145721
#
D - 7