Electro Industries Shark 200 Installation & Operation Manual page 207

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

Enable:
Scope:
---------------------------------------------------
Receive:
NOTE: This engages the log for use on this COM Port, and latches the oldest record as
record index 0.
3. Read [0xC757, 16 reg], Availability is 0.
Send:
Command:
Register Address:
# Registers:
---------------------------------------------------
Receive:
Data:
Max Records:
Num Records:
Record Size:
Log Availability:
First Timestamp:
Last Timestamp:
NOTE: This indicates that the log has been engaged properly in step 2. Proceed to
retrieve the log.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
B: Modbus Map and Retrieving Logs
1 (Engage log)
0 (Normal Mode)
0106C34F0280 (echo)
0103 C757 0010
0xC757
16
010320 00000100 00000064 0012 0002
060717101511 060718101511
0000000000000000
0x100 = 256 records maximum.
0x64 = 100 records currently logged.
0x12 = 18 bytes per record.
0x02 = 2, In use by COM2, RS485 (the current
port)
0x060717101511 = July 23, 2006, 16:21:17
0x060717101511 = July 24, 2006, 16:21:17
#
Doc
E149701
B-23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Shark 200t

Table of Contents