• The nodes "setTVTR1", "setTVTR2" and "setTVTR3" contain the ratio of the
voltage used by the measuring device.
• Any of the defined objects/ attributes can be placed within a dataset.
• The normal-speed in the Shark® 200 meter is measurements taken every second.
The energy counters are also updated every second.
The configuration of the devices takes place by converting the SCD file exported by
the System Configuration tool into a CID file. This CID file contains all of the informa-
tion from the SCD file which is needed for configuration by the EIG device. The tool is
named "SCDtoCIDConverter" and is a simple, publicly available program. The result-
ing CID file is then sent to the EIG device using HTTP file transfer.
E.1.4.1: Shark® 200 Server Configuration
The configuration file (CID) should be stored in the Shark® 200 meter in order to
configure the server. At power up the server reads the file, parses it and configures all
the internal settings for proper functionality.
Storing the CID file in the Shark® 200 meter is accomplished through its webpage.
The webpage allows the user to locate the CID file, and submit it to the Shark® 200
meter for storage.
The Shark® 200 meter does not need to be reset in order to accept the new configu-
ration, unless the IP address has been changed.
After storing the CID file, access the Shark® 200 meter's webpage again, to make
sure that the file has been stored, and to see if there is any problem with it, by check-
ing its status.
• A common problem you may see is IP mismatch (the IP address in the CID file
does not match the IP configured in the Shark® 200 meter's device profile). In this
case the Shark® 200 meter will use the IP address from its device profile, and the
IEC Server will work only with that address.
• If there is a critical error in the stored CID file, which prevents the IEC Server from
running, the CID file will not be used, and instead the Default CID file (embedded in
the server) will be used. The webpage will alert you to this situation.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
E: Using the IEC61850 Network Card
#
Doc
E149701
E-11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Shark 200t

Table of Contents