The Pulse Output/Digital Input card is a combination of pulse outputs via solid state
contacts and dry/wet contact sensing digital inputs. The outputs are electrically
isolated from the inputs and from the main unit.
7.7.1: Specifications
The technical specifications at 25 °C are as follows:
Power consumption:
Relay outputs:
Number of outputs:
Contact type:
Relay type:
Peak switching voltage:
Continuous load current:
Peak load current:
On resistance, max.:
Leakage current:
Switching Rate max.:
Isolation:
Reset/Power down state:
Inputs:
Number of inputs:
Sensing type:
Wetting voltage:
Input current:
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
7: Using the I/O Option Cards
0.420 W internal
4
Closing (SPST - NO)
Solid state
DC ±350 V
120 mA
350 mA for 10 ms
35
1µA@350 V
10/s
AC 3750 V system to contacts
Open contacts
4
Wet or dry contact status detection
DC (12-24) V, internally generated
2.5 mA – constant current regulated
#