20Ma Output Card (20Maos) - Electro Industries Shark 200 Installation & Operation Manual

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

7.5: 20mA Output Card (20mAOS)

The 20mA card transmits a standardized 0-20 mA signal. This signal is linearly pro-
portional to real-time quantities measured by the Shark® 200 meter. The current
sources need to be loop powered. The outputs are electrically isolated from the main
unit.
7.5.1: Specifications
The technical specifications at 25 °C at 500
Number of outputs:
Power consumption:
Signal output range:
Max. load impedance:
Hardware resolution:
Effective resolution:
Update rate per channel:
Output accuracy:
Load regulation:
Temperature coefficient
Isolation:
Maximum loop voltage:
Internal voltage drop:
Reset/Default output value:
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
7: Using the I/O Option Cards
load are as follows:
4 single ended
1 W internal
(0 to 24) mA
850 @ 24 V DC
12 bits
14 bits with 2.5 kHz PWM
100 ms
± 0.1% of output range (24 mA)
± 0.03% of output range (24 mA) load step of
200 @ 20 mA
± 300 n A/ °C
AC 2500 V system to outputs
28 V DC max.
3.4 V DC @ 24 mA
12 mA
#
Doc
E149701
7-7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Shark 200t

Table of Contents