Electro Industries Shark 200 Installation & Operation Manual page 94

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

For manual entry:
CT Ratios
CT Numerator (Primary): 1 - 9999
CT Denominator (Secondary): 5 or 1 A
NOTE: This field is display only.
Either CT Multiplier (Scaling): 1, 10 or 100
OR Ratio: the ratio to be applied, and click Update CT
Current Full Scale: Display only.
PT Ratios
PT Numerator (Primary): 1 - 9999
PT Denominator (Secondary): 40 - 600
PT Multiplier (Scaling): 1, 10, 100, or 1000
Voltage Full Scale: Display only.
System Wiring
3 Element Wye; 2.5 Element Wye; 2 CT Delta
Example Settings:
For a CT of 2000/5A, set the following CT Ratios in the entry fields:
CT Numerator (Primary)
CT Denominator (Secondary)
CT Multiplier
The Current Full Scale field will read 2000.
NOTE: You can obtain the same Current Full Scale by entering a CT Numerator of 200
and a CT Multiplier of 10.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
5: Communication Installation
2000
5
1
#
Doc
E149701
5-14