6.3: Understanding the % of Load Bar

The 10-segment LED bar graph at the bottom left of the Shark® 200 meter's front
panel provides a graphic representation of Amps. The segments light according to the
load, as shown in the table below.
When the load is over 120% of Full Load, all segments flash "On" (1.5 secs) and "Off"
(0.5 secs).
Segments
Load >= % Full Load
none
1
1%
1-2
15%
1-3
30%
1-4
45%
1-5
60%
1-6
72%
1-7
84%
1-8
96%
1-9
108%
1-10
120%
All Blink
>120%
The % of Load bar can be programmed through Communicator EXT
Chapter 8 in the Communicator EXT
Manual, for instructions.