from first event to report issuance), and integrity time (server periodic reports of all
data in dataset). The decision whether to use buffered or unbuffered must be decided
by the user.
Finally, in step 2 the System Configurator performs a consistency check and then out-
puts the SCD file. The SCD file is imported by the "ScdToCid" tool where the user
specifies the device name.
The resulting CID file is then imported into the target device.
E.1.4: Electro Industries' Implementation of the IEC 61850 Server
Following are features of EIG's IEC 61850 implementation:
• The lower-level addressing uses PSEL=00000001, SSEL=0001, and TSEL=0001.
• At the server level, each implements a single Logical Device name formed by con-
catenating the IED name (chosen by the System Configurator) and "Meas" (ex,
"MyDeviceMeas").
• The Logical Nodes implemented within the Logical Device include the standard LLN0
and LPHD1 with optional standard logical nodes in the "M" class (ex, "MMXU") and
"T" class (ex, "TVTR"). Each Logical Node contains only standardized objects of
standardized types (Common Data Class, CDC). The device is based upon the first
edition of the IEC 61850 standards.
Examples of Logical Nodes within the Shark® 200 family include eneMMTR1
(energy metering) and nsMMXU1 (normal speed Measurement Unit).
• The Shark® 200 device will get its IED name from the first <IED> section in the
configuration file (.cid). This name will be used for accessing its access point (IP
address) and its single Logical Device named "Meas". The IED name can be com-
posed of any string of up to 32 (alphanumeric only) characters.
• The logical nodes implemented in the Shark® 200 meter are listed below:
• The node "LLN0" keeps common information for the entire logical device. In this
node Datasets and Reports can be defined, based on the limitations provided in
the ICD file: the Shark® 200 meter supports up to 8 datasets with up to 256
attributes, and up to 16 report control blocks. The report control blocks and
datasets must be configured in the CID file, although the options, triggers and
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
E: Using the IEC61850 Network Card
#
Doc
E149701
E-9