System Event Record; B.5.5: Log Record Interpretation - Electro Industries Shark 200 Installation & Operation Manual

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

B.5.5: Log Record Interpretation

The records of each log are composed of a 6 byte timestamp, and N data. The content
of the data portion depends on the log.

System Event Record:

Byte
0
1
2
3
Value
timestamp
Size: 14 bytes (20 bytes image).
Data: The System Event data is 8 bytes; each byte is an enumerated value.
• Group: Group of the event.
• Event: Event within a group.
• Modifier: Additional information about the event, such as number of sectors or log
number.
• Channel: The port of the Shark® 200 meter that caused the event.
0
1
2
3
4
7
Param 1-4: These are defined for each event (see following table).
NOTE: The System Log Record is 20 bytes, consisting of the Record Header (12
bytes) and Payload (8 bytes). The Timestamp (6 bytes) is in the header. Typically,
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
4
5
6
7
8
Group
Event
Mod
Firmware
COM 1 (IrDA)
COM 2 (RS485)
COM 3 (Option Card 1)
COM 4 (Option Card 2)
User (Face Plate)
B: Modbus Map and Retrieving Logs
9
10
11
Chan
Param1
Param2
#
Doc
E149701
12
13
Param3
Param4
B-30

Hide quick links: