B.5.1: Data Formats

Time stamp: Stores a date from 2000 to 2099. Time stamp has a Minimum resolution
of 1 second.
Byte
Value
Range
Mask
The high bits of each time stamp byte are used as flags to record meter state
information at the time of the time stamp. These bits should be masked out, unless
needed.
B.5.2: Shark® 200 Meter Logs
The Shark® 200 meter has 7 logs: System Event, Alarm (Limits), 3 Historical, I/O
Change, and Waveform. Each log is described below.
1. System Event (0): The System Event log is used to store events which happen in,
and to, the meter. Events include Startup, Reset Commands, Log Retrievals, etc.
The System Event Log Record takes 20 bytes, 14 bytes of which are available when
the log is retrieved.
Byte
0
1
2
3
Value
timestamp
NOTE: The complete Systems Events table is shown in Section B.5.5, step 1, on page
B-30.
2. Alarm Log (1): The Alarm Log records the states of the 8 Limits programmed in
the meter.
• Whenever a limit goes out (above or below), a record is stored with the value
that caused the limit to go out.
• Whenever a limit returns within limit, a record is stored with the "most out of
limit" value for that limit while it was out of limit.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
0
1
Year
Month
0-99 (+2000)
1-12
0x7F
0x0F
4
5
6
7
8
Group
Event
Mod
B: Modbus Map and Retrieving Logs
2
3
4
Day
Hour
Minute
1-31
0-23
0-59
0x1F
0x1F
0x3F
9
10
11
Param1
Param2
Chan
#
Doc
E149701
5
Second
0-59
0x3F
12
13
Param3
Param4
B-4

Hide quick links:

Advertisement

Table of Contents
loading