4.5: Voltage and Power Supply Connections
Voltage inputs are connected to the back of the unit via optional wire connectors. The
connectors accommodate AWG# 12 -26/ (0.129 - 3.31) mm
4.6: Ground Connections
The meter's Ground terminals should be connected directly to the installation's
protective earth ground. Use AWG# 12/2.5 mm
4.7: Voltage Fuses
EIG requires the use of fuses on each of the sense voltages and on the control power.
• Use a 0.1 A fuse on each voltage input.
• Use a 3 A Slow Blow fuse on the power supply.
EIG offers the EI-CP Panel meter protective fuse kit, which can be ordered from EIG's
webstore: www.electroind.com/store. Select Fuse Kits from the list on the left side of
the webpage.