Modbus Address
Hex
Decimal
0C0F
-
0C10
3088 - 3089
VAR-hours, Net, Phase B
0C11
-
0C12
3090 - 3091
VAR-hours, Net, Phase C
0C13
-
0C14
3092 - 3093
VAR-hours, Total, Phase A
0C15
-
0C16
3094 - 3095
VAR-hours, Total, Phase B
0C17
-
0C18
3096 - 3097
VAR-hours, Total, Phase C
0C19
-
0C1A
3098 - 3099
VA-hours, Phase A
0C1B
-
0C1C
3100 - 3101
VA-hours, Phase B
0C1D
-
0C1E
3102 - 3103
VA-hours, Phase C
Phase Angle Block
1003
-
1003
4100 - 4100
Phase A Current
1004
-
1004
4101 - 4101
Phase B Current
1005
-
1005
4102 - 4102
Phase C Current
1006
-
1006
4103 - 4103
Angle, Volts A-B
1007
-
1007
4104 - 4104
Angle, Volts B-C
1008
-
1008
4105 - 4105
Angle, Volts C-A
Status Block
1193
-
1193
4500 - 4500
Port ID
1194
-
1194
4501 - 4501
Meter Status
1195
-
1195
4502 - 4502
Limits Status
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1)
Format
Range (Note 6)
SINT32
-99999999 to 99999999 VARh per energy format
SINT32
-99999999 to 99999999 VARh per energy format
SINT32
0 to 99999999
SINT32
0 to 99999999
SINT32
0 to 99999999
SINT32
0 to 99999999
SINT32
0 to 99999999
SINT32
0 to 99999999
SINT16
-1800 to +1800
SINT16
-1800 to +1800
SINT16
-1800 to +1800
SINT16
-1800 to +1800
SINT16
-1800 to +1800
SINT16
-1800 to +1800
UINT16
1 to 4
UINT16
bit-mapped
UINT16
bit-mapped
Doc# E149701
B: Modbus Map and Retrieving Logs
Units or Resolution
VARh per energy format
VARh per energy format
VARh per energy format
VAh per energy format
VAh per energy format
VAh per energy format
0.1 degree
0.1 degree
0.1 degree
0.1 degree
0.1 degree
0.1 degree
none
Identifies which Shark COM port a master is connected
to; 1 for COM1, 2 for COM2, etc.
mmmpch-- tffeeccc
mmm = measurement state (0=off, 1=running normally,
2=limp mode, 3=warmup, 6&7=boot, others unused)
See note 16.
pch = NVMEM block OK flags (p=profile, c=calibration,
h=header), flag is 1 if OK
t - CT PT compensation status. (0=Disabled,1=Enabled)
ff = flash state (0=initializing, 1=logging disabled by
Vswitch, 3=logging)
ee = edit state (0=startup, 1=normal, 2=privileged
command session, 3=profile update mode)
ccc = port enabled for edit(0=none, 1-4=COM1-COM4,
7=front panel)
87654321 87654321
high byte is setpt 1, 0=in, 1=out
low byte is setpt 2, 0=in, 1=out
see notes 11, 12, 17
Comments
# Reg
2
2
2
2
2
2
2
2
Block Size:
104
read-only
1
1
1
1
1
1
Block Size:
6
read-only
1
1
1
MM-10